| Parameter | Värde |
|---|---|
| Punkt | Specifications |
| Produkt | FP7 High-speed Counter Units |
| Artikelnummer | AFP7HSC4T |
| Produktnamn | FP7 High-speed Counter |
| Produktnummer | AFP7HSC4T |
| Inmatning: Isoleringsmetod | Photocoupler insulation |
| Ingång: Nominell ingångsspänning | 12 to 24 V DC / 3.5 to 5 V DC |
| Räknefunktion: Räknetyp | Linear counter / Ring counter |
| Räknefunktion: Extern I/O | Control signal input: 8 points (2 points/ch), External output: 8 points (2 points/ch) |
| Räknefunktion: Ingångssignal | Phases A, B and Z |
| Ingång: Ingångsimpedans: 5 V DC | 390 Ohm (5 V DC) approx. |
| Räknefunktion: Räkneområde | Signed 32-bit (-2,147,483,648 to +2,147,483,647) |
| Ingång: Ingångsimpedans: 24 V DC | 3.0 kOhm approx. |
| Räknefunktion: Antal räknare | 4ch |
| Ingång: Användningsspänningsområde: 5 V DC | 3.5 to 5.25 V DC |
| Andra funktioner: Inspelningsfunktion | Acquires the current count value from the edges of input signals, and stores it in the capture 0 register or capture 1 register. The value of the specified capture register will be overwritten by a new value and the old value will be discarded every time a counter value is captured. |
| Räknefunktion: Räknaringångstyp | Individual input (Phases A and B): 1 multiple, 2-multipleDirection discrimination input: 1 multiple, 2-multiple2-phase input: 1 multiple, 2-multiple, 4-multiple |
| Ingång: Inställning av tidskonstant för ingång | None, 0.1 micro s, 0.2 micro s, 0.5 micro s, 1.0 micro s, 2.0 micro s and 10.0 micro s |
| Ingång: Användningsspänningsområde: 24 V DC | 10.8 to 26.4 V DC |
| Räknefunktion: Max. ingångsfrekvens | 4 MHz / 8 MHz for individual input (phases A and B) (Duty ratio 50 plus or minus 10 %), 4 MHz / 8 MHz for direction discrimination input (Duty ratio 50 plus or minus 10 %), 4 MHz / 8 MHz /16 MHz for 2-phase input (Duty ratio 50 plus or minus 10 %, Phase shifting below 5 %) |
| Andra funktioner: Avbrottsfunktion för ingång | Available (2 points/ch, Max. 8 points/unit)(Note) The interrupt input function can be used for 8 points per unit and for a maximum of 8 units (max. 64 points) in the whole system. However, the entire scan time slows down as more interrupt programs are used. Minimize the use of interrupt programs.(Note) The priority order for interrupt inputs is as follows; In a unit, from the smallest interrupt bit. In the whole system, from the smallest unit number. |
| Ingång: Min. PÅ-spänning / Min. PÅ-ström: 5 V DC | 3.0 V DC / 4 mA |
| Jämförelsefunktion: Funktion för matchning av målvärde | Depending on the count direction, sets or resets the output when the counter value reaches the target value. |
| Ingång: Min. PÅ-spänning / Min. PÅ-ström: 24 V DC | 10 V DC / 4 mA |
| Ingång: Max. AV-spänning / Max. AV-ström: 5 V DC | 1.0 V DC / 0.5 mA |
| Extern utgång: Jämförelseresultatutgångsfunktion | Outputs the result of comparison function. |
| Ingång: Max. AV-spänning / Max. AV-ström: 24 V DC | 2.0 V DC / 2 mA |
| Mätfunktion: Frekvensmätningsfunktion | Measures the intervals between the variations of count values, and calculates the frequency. |
Tekniska specifikationer och prestandadata
Installations- och bruksanvisning