| Parameter | Värde |
|---|---|
| EAN () | 5702421803271 |
| Typ () | VFG 2 |
| Volym () | 180 Liter |
| Funktion () | Pressure relief |
| Nettovikt () | 73.5 Kilogram |
| Ventilstorlek () | DN 125 |
| Applikation () | District Heating |
| Beskrivning () | VFG2 PN25 125/160 2-way flange flow/ret |
| Slaglängd [mm] () | 20 mm |
| Bruttovikt () | 73.5 Kilogram |
| Diameter [mm] () | 125 mm |
| Produktgrupp () | Pressure flow controllers |
| Mediets pH [Max] () | 10 |
| Mediets pH [Min] () | 7 |
| Tryckklass () | PN 25 |
| Antal portar () | 2 |
| Anslutningstyper () | Flange |
| Monteringsversion () | Free |
| Spindelposition () | Normally open |
| Kavitationsfaktor () | 0.35 |
| Tillåtna medier () | District heating/cooling circulation water |
| EU RoHS-överensstämmelse () | Out of scope |
| Kvs-värden [m³/h] () | 160 m³/h |
| Medelalternativ () | Glycolic water up to 30% |
| Överensstämmelse med RoHS i Storbritannien () | Out of scope |
| Flödeskarakteristik () | Linear optimized |
| Ventilhusmaterial () | Ductile cast iron EN-GJS-400-18-LT (GGG 40.3) |
| Ventilkonmaterial () | Stainless steel, mat. No. 1.4404 |
| Ventilsätesmaterial () | Stainless steel, mat. No. 1.4021 |
| Kavitationsfaktor 25 % () | 0.5 |
| Kavitationsfaktor 50 % () | 0.42 |
| Kavitationsfaktor 75 % () | 0.35 |
| Kinas RoHS-efterlevnad () | Out of scope |
| Kavitationsfaktor 100 % () | 0.28 |
| Nominellt tryck [bar] () | 25 bar |
| Medietemperatur [°C] [Max] () | 200 °C |
| Medietemperatur [°C] [Min] () | 2 °C |
| Ämnen på kandidatlistan för REACH ( | No |
| Läckage genom port max. [% Kvs] () | 0.03 |
| Ingår i WEEE-systemet och innehåller batterier () | No |
| Differenstryckområde [bar] [Max] () | 15 bar |
Tekniska specifikationer och prestandadata